Calculations
Discipline-by-discipline engineering calculations — electrical, HVAC, acoustic, seismic, fuel, pressure. Licensed software plus empirical validation. No skipped numbers.
Right standard for every discipline. Right calculation for every path. No skipped numbers.
Most engineering firms “size” — they pick a rated power, mark a model from the catalogue and move on. But making a power system actually work on site requires far more calculation. We model every path in the system: the electrical path, the fuel path, the air path, the acoustic path, the mechanical-load path.
What happens when you don’t? Radiators that won’t reject heat. Transfer switches that fail under arc-flash. Silencers that don’t attenuate enough. Acoustic complaints. Stored fuel that degrades because the day-tank loop was wrong. We calculate all of these.
Calculation categories
1. Capacity
- Load profile analysis — continuous, peak, transient, motor-starting
- Sizing methodology — derating (altitude, temperature, fuel type), redundancy (N, N+1, 2N)
- Future expansion — 5- and 10-year projection
Standards: ISO 8528-1, NFPA 110, IEEE 446
2. Electrical
- Load flow — steady-state current / voltage distribution
- Short circuit (IEC 60909) — symmetrical / asymmetrical fault current, peak
- Arc flash (IEEE 1584) — incident energy, PPE category, approach boundaries
- Coordination — selectivity, breaker / relay settings, IEEE C37
- Harmonics (IEEE 519 / IEC 61000) — THD limits, filter sizing
- Motor starting — DOL, soft-start, VFD comparison
- Voltage dip & transient — UPS compatibility, ITIC curve
3. Fuel system
- Storage sizing — 24h / 72h / 7-day runtime + redundancy
- Day tank — gravity feed vs transfer pump, return loop
- Polishing — particulate + moisture + biological contamination filtration
- Pressure drop — pipe sizing, vent area, dip-tube analysis
- Spill containment — bund volume, leak detection (EN 13160)
Standards: EN 12285, KIWA BRL-K903, BS 799, UL 142, API 650, NFPA 30, NFPA 37
4. ★ HVAC / Ventilation / Cooling — the most commonly-skipped calculation
Most generator rooms fail their first heat-rejection test. The reason is almost always the same: the radiator fan’s static-pressure capacity is below the total pressure drop the airflow has to overcome. Sometimes the opposite — fan capacity far exceeds the rest of the room and the room runs in vacuum; result: the door won’t open, and when it does open it does so with a force above the HSE limit.
The path we calculate:
[Outside air — entry at alternator end]
↓ ΔP₁ = inlet louver resistance
[Filter / pre-filter]
↓ ΔP₂ = filter pressure drop (with dirty allowance)
[Inside room: alternator → engine traverse]
↓ ΔP₃ = ducting + change-of-direction losses
[Radiator core (with fan)]
↓ ΔP₄ = heat-exchanger side resistance
[Discharge ducting + exhaust louver — exit at radiator end]
↓ ΔP₅ = exit resistance
[Outside]
Σ ΔP < fan static-pressure capacity (× safety factor)
Plus: free-cooling strategy (Europe DC requirement), hot / cold aisle isolation (data centre), make-up air balance.
Standards: ASHRAE 90.1, ASHRAE Handbook, ASHRAE TC 9.9 (mission critical), EN 13779, AMCA 210, NEBB, NFPA 90A
5. ★ Acoustics (intake / room / exhaust + structural)
Acoustic engineering is sound propagation along three separate paths. Many firms add a muffler and stop there. We model all three:
[Genset (source)]
├──▶ INTAKE PATH: room → intake louver → outside
├──▶ EXHAUST PATH: engine → silencer → stack → outside
└──▶ STRUCTURAL PATH: enclosure wall + floor + ceiling (transmission loss)
Insertion loss is calculated for each path separately, then summed logarithmically with:
- Distance attenuation (free field / hemi-sphere)
- Ground absorption
- Atmospheric absorption
- Building reflections
- Regulatory limit (day / night, distance-weighted)
Standards: ISO 3744, ISO 3746, ISO 8528-10, ISO 9612, BS 4142, EU Outdoor Noise Directive 2000/14, ANSI S12.18, ASHRAE Handbook (Sound & Vibration Control)
6. Seismic
Post-earthquake operability is critical: the grid is down, the generator is the only source. The system must survive and remain functional.
- Skid — base-frame deformation, generator attachment
- Enclosure — structural + internal equipment attachment
- Day tank — anchorage including slosh load
- Switchgear seismic qualification — IEEE 693
Standards: ASCE 7, IBC, Eurocode 8 (EN 1998), AISC 360 + 341, IEEE 693, TS 498 / TBDY 2018 (Türkiye)
7. Pressure (air, water, fuel)
- Air — radiator + intake / exhaust, compressed-air system (where used)
- Water — coolant loop, heat exchanger, jacket-water expansion
- Fuel — line pressure, vent area, day-tank vacuum / positive-pressure limits
Standards: Manufacturer limits, ASME B31.1 (power piping), API 14E (oil & gas piping)
Software
We use licensed engineering software plus empirical validation. Every calculation runs through at least two methods.
| Discipline | Tools |
|---|---|
| Electrical | ETAP, DigSilent PowerFactory |
| Fuel + HVAC | ASHRAE tables + NEC + Excel / Mathcad / custom Python |
| Acoustics | NEC Acoustix, ASHRAE-method custom calculation sheets |
| CFD (ventilation simulation) — independent value-add | Custom Python + ANSYS Fluent |
| Seismic | Custom Python + ANSYS Mechanical |
| Sizing cross-check | OE sizing tools (multiple vendors compared) |